Potable Water Design Standards/Page 1 of 24/March 2023
SECTION 2 - POTABLE WATER SYSTEM
2.1 POTABLE WATER DESIGN
There shall be no physical connection between an active Potable Water supply and an unapproved
water supply, or any reclaimed water, wastewater or storm water system, which would allow
unsafe water to enter or backflow into the active Potable Water system by direct pressure, vacuum,
gravity or any other means. All Potable Water services shall be compliant with all applicable cross
connection regulations. All brass in contact with Potable Water shall be “Lead Free”.
Design standards for Potable Water mains (WM) are as follows with Raw Water mains being
designed and constructed to Potable Water main standards.
(a) Minimum Cover:
Design finished grade over WM shall be 36" minimum (30” is acceptable with ductile iron pipe
(DIP) except for pipes under proposed/existing pavement in public rights-of-way) and 60”
maximum unless otherwise approved by the Department prior to the start of construction. All
Potable Water transmission mains within major thoroughfare rights of way shall have full plan and
profiles shown. Water main pipes designed to be as level as possible to avoid high points. Proposed
top of pipe elevations shall be shown at 100’ intervals on the design plan views prior to Department
approval. Reduced minimum cover below 36” requires prior approval by the Department.
(b) Minimum Horizontal Separation (outside wall to outside wall):
(1) 10’ to buildings, exfiltration trenches, roof overhangs, canopies, walls, fountains, and
other similar structures.
(2) 10’ to Wastewater lines (6’ minimum may be allowed in special circumstances and only
with prior Department approval).
(3) 10' to drainage pipes (3’ minimum may be allowed in special circumstances and only
with prior Department approval).
(4) 10’ to electrical conduits and communication conduits (6’ minimum may be allowed in
special circumstances and only with prior Department approval).
(5) 6’ minimum to power poles and light poles. (4’ minimum may be allowed in special
circumstancess and only with prior Department approval).
(6) 6’ minimum to drainage structures. (3’ minimum may be allowed in special
circumstancess and only with prior Department approval).
(7) 10’ minimum to reclaimed water lines (6minimum may be allowed in special
circumstancess and only with prior Department approval).
(c) Vertical Separation:
(1) 12” minimum separation between all pipes should be maintained. However a minimum of
6" vertical separation is acceptable if it is not possible to maintain 12” and if the water main
crosses over a storm or wastewater gravity main with a section of water main being DIP
centered on crossing with prior Department approval. When there is no alternative to the
Potable Water Design Standards/Page 2 of 24/March 2023
water main passing under a storm or wastewater gravity main, and when the water main
crosses over or under a reclaimed water main, or force main (wastewater or stormwater), a
minimum of 12” vertical clearance shall be maintained with no exceptions with a section
of water main centered on the crossing.
(2) WM shall cross over gas mains, electrical conduits, and communication conduits unless
not feasible. No matter if WM crosses over or under gas mains, electrical conduits, and
communication conduits a minimum of 18” vertical separation shall be maintained unless
previously approved by the Department.
(d) Layout:
(1) The Potable Water mains shall be looped unless otherwise not feasible. Multiple feed lines
may be required at discretion of the Department. Permanent “dead ends” are not acceptable
unless unavoidable. If a permanent dead end, remaining longer than one year is required,
then an automatic flushing device to be installed to maintain water quality. On residential
dead end streets, with or without cul-de-sacs, the WM is required to be looped around the
dead end street to avoid long water services and/or the installation of an automatic flushing
device. If a temporary dead end is required for future water main extension, less than one
year, a temporary blow-off may be allowed in those circumstances and only with prior
Department approval if the WM cannot be looped to avoid the installation of a temporary
blow-off.
(2) WM should be placed in road right-of-ways (ROWs) or dedicated common tracts whenever
possible. WM shall be located under sidewalks in residential areas unless not feasible due
to project conditions and with prior Department approval. Placement of WM on or adjacent
to interior property lines or between structures is discouraged and will be approved only
when unavoidable or when necessary for looping. Water mains shall not be placed in
ditches, landscape buffers, wetlands, or storm water management areas unless special
circumstances require water main to be installed in those area and then only with prior
Department approval.
(3) Details of connections to existing facilities must be shown. A reverse tap due to pre-
existing conditions are acceptable only if approved by the Department (detailed to scale
plan and profile are required).
(4) In order to facilitate Potable Water service for all properties within the service area, Potable
Water mains shall be extended along the full length of all fronting boundaries of a property
by the Developer/Owner requesting Potable Water service. Potable Water mains may be
required to be extended through the property if another is to be served in the future at the
Department’s discretion.
(5) Loop Potable Water main to existing Potable Water mains or leave provisions for looping
or extension whenever possible. The mains in such instances shall end with a valve and
plug. Water mains 16” and larger shall end with a teed off fire hydrant, inline valve and
plug. The valve shall be mechanically restrained.
Potable Water Design Standards/Page 3 of 24/March 2023
(6) Sample points shall be depicted on design plans with a sample point being required at the
source of connection, at all dead ends, at any branching intersections and shall not exceed
1,200 feet between sample points.
(7) When a Potable Water main crosses a fence of any material, a wall of any type (panel,
concrete block, etc.) or a berm higher than two (2) feet in height the water main is required
to be within a steel casing. The casing is required to extend three (3) feet minimum beyond
either side of the berm or ten (10) feet minimum beyond either side of a fence or wall
whichever is greater, see Standard Detail 48W.
(8) When a Potable Water main design requires the main to cross under a storm water pipe
larger than thirty (30) inches in diameter the Department reserves the right to require the
storm water pipe to be redesigned not to exceed thirty (30) inches in diameter. If
redesigning the storm water system is not an option then the Potable Water main must be
ductile iron pipe (DIP). The Department reserves the right to require the main to be located
within a steel casing or relocate the main to avoid the storm water pipe crossing.
(9) When a new or existing WM is in conflict with a new or existing storm water pipe and the
WM cannot deflect around the storm water pipe due to special circumstances a conflict
structure may be accepted. If a conflict structure must be installed its design must meet
both Florida Department of Transportation (FDOT) and Palm Beach County Water
Utilities Department (WUD) Minimum Design and Construction Standards with prior
Department and Florida Department of Environmental Protection (FDEP) approval.
(e) Potable Water Main Material:
Pressure Class Rated or Special Thickness Class Rated Cement Lined Ductile Iron Pipe (DIP)
or C-900 Class 150 DR 18 PVC pipe (Color: Blue) shall be allowed for WM 12" diameter or
smaller. The lining for DIP shall be factory applied in accordance with the manufacturer’s
specifications and shall be warranted by the pipe manufacturers. Unless specific approval is
granted, no water main shall be encased in concrete. Potable Water mains shall be marked
with one continuous strip of 6" wide magnetic blue coded tape imprinted with one and one-
half (1 1/2) inch high lettering reading "Caution Water Line Below", and located
approximately twelve (12) inches above the crown of the pipe. The wording shall occur every
three (3) feet. Buried DIP smaller than 24” shall be painted with a 4” wide continuous blue
line parallel to the axis of the pipe and that is located on top of pipe. Buried DIP 24” and
larger shall have a 4” wide continuous blue line applied along each side of pipe as well as
along the top of pipe. The coating shall be minimum 8 mils WFT, and minimum 3 mils DFT.
DIP shall be required in the following circumstances:
(1) WM 16" in diameter or larger.
(2) WM smaller than 6".
(3) Within 10' of Wastewater/ storm/reclaimed water pipes for parallel installation.
(4) Within 15' of structures, (near side of concrete footing), and top of bank of canals or lakes.
Potable Water Design Standards/Page 4 of 24/March 2023
(5) Crossings over Wastewater, reclaimed water and storm pipes with less than 12”
separation with no joint within 10' of each other; crossings under any Wastewater,
reclaimed water or storm pipe.
(6) Jack and bores (mechanical joints with "Megalugs" or equal).
(7) Potable Water mains for fire sprinkler system connections up to point of service.
(8) Fire hydrant branches from water main tee to fire hydrant.
(9) Fire line branches up to point of service valve with or without a water service line
connected to the fire line branch between the WM and point of service valve.
(10) The Department reserves the right to mandate DIP within public ROWs, any instances
of off-site or on-site construction where future damage to the line is possible due to
location or circumstances, or in private property away from dedicated ROWs.
(11) Flanged ductile iron pipe is required for exposed (not buried) installation.
(12) Ductile iron pipe shall be polywrapped if buried closer than 10’ to other underground
iron/steel pipes if no other protection is provided.
(13) Water main with less than 36” cover over pipe with prior Department approval.
(14) Where required for locations with substandard separations to other piping systems.
(f) Potable Water Main Size:
The WM shall be sized by the developer's engineer as required. The Department's Master
Planning may require a greater diameter. An over sizing credit as defined in Chapter 3 of the
Department's Uniform Policies and Procedures Manual (UPAP) may apply. Use the “Friction
Coefficient Factor" C=120 for flow calculations and a peak instantaneous flow velocity of 3
feet per second to determine applicable credits.
The minimum size of WM shall be 6". Four-inch (4") mains may be proposed for non-fire
hydrant lines serving cul-de-sacs where additional development will not occur. The engineer
may be required to demonstrate the adequacy of such sizing. In cases where the completion
of gaps in the Potable Water systems to meet flow requirements of the development is
necessary, the developer shall construct the required improvements. Delivered flows shall
meet peak domestic requirements as mandated by State DEP plus fire flow as mandated by the
Fire Marshal. Domestic average flows shall be based on 270 gpd per Equivalent Residential
Connection. The residual pressure under these conditions shall not be less than 20 psi. Potable
Water Main sizes shall conform to the latest Department Potable Water Master Plan.
(g) Valves and Appurtenances:
(1) Valves - Valving of all systems shall be designed to facilitate the isolation of each section
of pipeline between intersections of the grid system. Generally, the number of valves at an
intersection shall be one less than the number of pipes forming the intersection.
All valves shall have mechanical joint or flanged ends and be of resilient seat design with
right hand closed operation; valves 12" or greater shall be butterfly valves unless another
type of valve is approved in writing by the Department prior to installation. Butterfly valves
larger than 16” shall have worm gears. Valves shall be certified for buried service if
applicable. Valves 24” and smaller shall be rated min. 150 psi. Larger valves shall be rated
Potable Water Design Standards/Page 5 of 24/March 2023
min. 200 psi.
In-line valves shall be installed for mains 16” and smaller near each side of a canal crossing
and/or major road crossing.
In-line valves shall generally be installed at intervals no greater than 1,000 feet on
transmission mains, at intervals of no greater than 700 LF on main distribution loops and
feeders, and on all primary branches connected to these mains. In high-density areas, valves
shall be installed as necessary to minimize the number of persons affected by a break. In
all instances, effectiveness of placement shall be primary criteria in determining valve
location. Valves placed in curbs will not be accepted. When located in traffic areas, valves
shall be placed in center of traffic lanes. All valves require lids and must be marked "water".
All valves shall be numerically identified on construction drawings.
The Department reserves the right to require additional valves at their discretion.
Clearance of 18" or one pipe diameter, whichever is greater, shall be maintained between
all fittings (bells, valves, saddles, flanges, etc.).
(2) Combination Air Release Valves shall be installed at all canal crossings and at high points.
Combination air release valves shall be sized per manufacturer’s recommendations.
(3) All fittings, bends, crosses and caps shall have mechanical joint or flanged ends unless an
approved flexible joint restraint system is used.
(h) Thrust Restraint:
(1) All bends, tees, crosses, reducers, valves and dead ends shall be restrained through an
approved means of mechanical or approved flexible joint restraint. Thrust blocks consisting
of poured-in-place concrete having a minimum compressive strength of 2,500 psi after 28
days cure may be utilized only with prior approval for connections to existing un-restrained
piping. Any line terminated as a construction phase that is a known future extension, shall
have a plugged valve placed at the end, and restrained with approved mechanical or flexible
joint restraint.
(2) An adequate number of pipe lengths shall be restrained using approved mechanical joint
restraints (MJ pipe), flexible joint restraints (DIP push-on joint pipe) or pressure pipe bell
restraints (PVC or DIP push-on joint pipe) to handle 150 psi working pressure and 250 psi
surge pressure. Pipes larger than 24” shall be restrained and pressure tested to 200 psi. If
the restraint pipe length on a design deviates from the standard length listed herein in the
restrained pipe lengths shall be designed by a Registered Engineer based upon the soil
conditions and shall be shown on the design drawings and record drawings.
Potable Water Design Standards/Page 6 of 24/March 2023
(3) If flexible joint restraints are utilized, the following requirements must be met:
The installation of flexible joint restraints must be witnessed by a Construction
Coordinator.
A copy of the material invoice must be available on the job site for review to
confirm the shipment of restraining gaskets, etc.
(4) PVC/DI pipe transitioning from HDPE pipe shall be restrained as a minimum to “in-line
valve” condition.
Potable Water Design Standards/Page 7 of 24/March 2023
7. DESIGN ENGINEER IS RESPONSIBLE TO PROPERLY SIZE THE RESTRAINT PIPE LENGTHS FOR THE
PROJECTS.
Potable Water Design Standards/Page 8 of 24/March 2023
Notes:
The data in the above table are based upon the following installation conditions:
Soil Type Sand
Test Pressure – 150 psi up to 24”, 200 psi for pipes larger than 24”.
Depth of Bury – 3’
Trench Type – 3
Safety Factor – 1.5
Vertical Off-Set – 3’
Minimum pipe length along tee run – 5’
The restrained pipe lengths apply to PVC pipe and DIP without polyethylene encasement.
All joints between upper and lower bends shall be restrained.
Restrained pipe lengths apply to pipe on both sides of valves and fittings.
The above table shall serve as a general design and construction guide only. It is the Engineer’s
responsibility to justify and document any deviations from the pipe lengths specified in the above
table.
i. Fire Hydrants and Fire Sprinkler Systems:
The appropriate Fire Marshal has final jurisdiction on fire flow requirements, on hydrant
locations and fire sprinkler system requirements. An original Fire Marshal stamped approved
plan is required with each project submission and a revised Fire Marshal stamped approved plan
is required with any revision that relocates a hydrant or a fire line connection more than 5’ from
its original Fire Marshal approved location. An approved above ground Double Check Detector
Valve Assembly (DCDA) or Reduced Pressure Principle Detector Assembly (RPDA) shall be
installed prior to Service Activation on all dedicated fire lines.
(1) Fire Hydrants - Fire hydrants shall be provided in all Potable Water distribution systems and
shall have a 5-1/4" main valve. Each hydrant shall be equipped with approved locking caps
(with chains). The caps must be installed prior to water system certification. Fire hydrants
shall be spaced such that the fire apparatus driving distance between fire hydrants does not
exceed 800 feet within residential areas and 500 feet within non-residential areas, or as
approved by the Fire Marshal. In new developments, both residential and non-residential,
the water distribution system shall be capable of delivering a minimum fire flow at 20 PSI.
A minimum fire flow of 1,500 gallons per minute (GPM) is required for non-fire sprinkled
buildings. Then a minimum fire flow of 1,000 GPM is acceptable if all buildings within an
individual fire hydrant zone are fire sprinkled. In either case, the Fire Marshal at their
discretion may require a higher fire flow. Multiple fire hydrants with looped mains and/or
larger main sizes may be required to provide adequate level of fire protection for projects
with higher flow demand. The Fire Marshal or designee having jurisdiction shall perform
flow tests to verify the specified fire flow demand prior to final FDEP certification.
Fire hydrant branches (from main to hydrant) shall not be less than 6" ID being DIP material
and be as short as possible to minimize any potential for a Potable Water main with no flow.
Potable Water Design Standards/Page 9 of 24/March 2023
Each branch shall be restrained and provided with a gate valve. Hydrants shall be located
minimum five feet from edge of road pavement with raised curbing, minimum six feet from
edge of road pavement without raised curbing and no less than three (3’) feet from driveways
with the pumper discharge nozzle facing the roadway. Hydrants shall be located so as to
minimize their vulnerability to traffic. Bollards shall be shown on the design plans and
installed where required. Bollards are not allowed within “Clear Zones” in thoroughfare plan
roads. On transmission mains, fire hydrants shall be spaced as required by the Fire Marshal
and to serve as sample points for bacteriological testing.
Fire hydrants shall be placed in an accessible, unobstructed location with 7.5' minimum
clearance in all directions unless otherwise previously approved by the Fire Marshal and the
Department. Fire hydrants shall be numerically identified on construction drawings. New
private fire hydrants are not allowed and all new fire hydrants shall be owned and maintained
by the Department. Existing privately owned dedicated fire hydrant lines shall be separated
from Department owned water mains by a privately owned DCDA.
(2) Fire Sprinkler System Connections
Fire sprinkler branches from main to a fire line type of device (IE DCDA, DDCV, etc.) shall
not be less than 4" ID being DIP material and be as short as possible to minimize any potential
for a Potable Water main with no flow. Each branch shall be restrained and provided with a
gate valve just prior (18” minimum to 24” maximum without prior Department approval) to
the initial vertical 90 degree bend for the fire line device assembly which is the point of
service valve for the Department. No connections permitted between the point of service
valve and the fire line device assembly without prior Department approval.
Residential fire sprinkler systems (NFPA type 13d). There shall be no separate service
connection to the potable water system. The sprinkler system shall be connected to the
domestic water service line on the customer side of the water meter. A minimum 1” water
service line and a minimum 1” meter are required to assure adequate flow rate. As a
minimum, an in-line check valve is required at the Point of Connection of the fire line into
the domestic service line to prevent backflow. It is the property owner’s responsibility to
obtain any necessary permits and certifications for the fire sprinkler system.
NFPA type 13r fire sprinkler systems. Fire sprinkler system branches shall be minimum 4”
ductile iron pipe up to Point of Service. Closed dedicated fire sprinkler connections shall
require as minimum backflow prevention devise a double check detector assembly (DCDA).
Sprinkler systems with pressure/storage tanks, booster pumps, chemical additive injection
systems, and/or auxiliary water supply connections shall require reduced pressure principle
detector assembly. Pressure testing and inspection of the Department’s water distribution
system shall be performed as a minimum up to the valve designated as the Point of Service
(see Standard Detail). The Department shall perform the initial testing and certification of
the backflow prevention assembly prior to Service Activation. All subsequent tests and
certifications are the responsibility of the Property Owner. There shall be no pipe joints or
any service connections between the point of fire service valve and first 90 degrees bend
Potable Water Design Standards/Page 10 of 24/March 2023
leading up to the backflow prevention assembly. The design shall minimize any potential
for Potable Water main with no flow.
The design and construction of privately owned fire lines shall conform to the applicable
Fire Marshal standards pertaining to dedicated fire sprinkler systems (i.e., the installation
of tamper switches and post indicator valves may be required).
(j) Potable Water Service Lines and Taps:
Potable Water service taps on the main shall be spaced at a minimum distance of 18" apart or
greater, as shown on details. All PVC service lines shall be Schedule 40 PVC with Schedule 80
fittings. Polyethylene services shall be PE 3408/3608 CTS DR9 blue or blue striped for water
service lines 1½” or smaller only. All water services shall be of the same material on the same
project unless previously approved by the Department prior to the start of construction. Services
shall be installed in accordance with the construction details of this manual and shall have
corporation stops. 1½” corporation stops and double strap saddles shall be required for 5/8" X
3/4" and 1" meters. 2" corporation stops and double strap saddles shall be required for 1-1/2"
and 2" meters. The threaded area of a corporation stop shall be spiral wrapped with two wraps
of Teflon tape. The corporation stop shall not be bottomed out (1-3 threads remain showing).
A valve box shall be installed over all 2” corporation stops and on corporation stops located
within pavement areas. Compression (pack joint) style adapters shall be used for transition
from brass valves and fitting to PVC pipes.
No PVC male/female adapters shall be used. Services shall not exceed 100' to the meter.
Services crossing under parking tracts shall have their meters placed prior to the crossing so that
the Department is not responsible for these lines.
In developments where the property line is not clearly defined (condominiums and commercial),
the meter shall be placed in a readily accessible location. Service lines under driveways and
roadways shall be encased in minimum three (3) inch casing (black iron, PVC Schedule 40 or
HDPE Pipe). Service taps under driveways and roadways shall be avoided whenever possible.
For water meter installations within nonexclusive utility easement paralleling a road right-of-
way, the control valve shall be located a maximum of 18” from the right-of-way line and the
meter box shall not extend into the easement by more than 48” from the right-of-way line.
Private services shall not cross Potable Water mains unless specifically identified on plans and
approved by the Department. The Developer shall coordinate the installation of private service
lines with location of meters to deliver Potable Water to the correct multi-family dwelling unit
or bay and shall identify each to the Department. The water meter location shall match the site
plan layout to eliminate service line crossings.
Wet Taps equal or larger than one half the pipe’s diameter require a restrained ductile iron
mechanical joint tapping sleeve. No size on size taps are permitted except on DIP with prior
Department approval.
Potable Water Design Standards/Page 11 of 24/March 2023
(k) Potable Water Meter Installation:
General requirement - Construction plans shall include a typical meter installation detail for
each size meter to be installed. Service line and meter sizes must be shown on the plans. Dual
metering of a single building service (i.e., two 1" meters instead of one 2" meter) shall not be
permitted. The proper sizing of meters and service lines is the responsibility of the developer's
engineer. Meters will be available in the following sizes only: 5/8" X 3/4", 1", 1-1/2", 2", 3",
4" and larger sizes as necessary. Meter boxes for 4" and smaller meters are standard. A bypass
will be required for meters 1-1/2" and larger (see details). A project consisting of multiple
services shall use the same pipe material for all services (where applicable). Service pipe
material shall be identified on record drawing.
All applicable Service Initiation Fees must be paid to the Department prior to meter installation,
and all meters will be installed by the Department. All service piping, valves, lids, boxes and
required backflow prevention assemblies/devices must be built in accordance to these
standards prior to meter installation. Generally, the Department will not install services for
meters 3" and larger.
The number of metered connections shall match the number of connections reserved. The
meter location and layout shall be determined prior to plan approval. Commercial
establishments with Grease Traps, Oil/Grease Interceptors and/or Sand/Oil Interceptors shall
be individually metered through the Department.
Consideration shall be given to the plumbing system in master metered projects, so water and
sewer service can be provided individually in the future, if so desired or required.
No tapping of a WUD potable water transmission main is permitted for water meter services.
A transmission main is any potable water pipe sixteen (16) inches or larger in pipe diameter
that is designed to move large quantities of water from the supply source, water treatment plant,
to smaller distribution mains being twelve (12) inches or smaller in pipe diameter.
(l) Water meter boxes:
All meter boxes and lids shall display the manufacturer’s name.
All meter boxes shall display the date of manufacture.
Traffic rated boxes and lids are required for all boxes in hardscaped area.
Meter box lids to be “RF” compatible.
Location requirement - Meters shall generally be set in grass area generally at or near a
common property line unless shown otherwise on approved plans.
Meter boxes for "zero lot line" properties shall be set in grass area as close as possible to a
common property line. An installation detail shall be added to each plan sheet.
Potable Water Design Standards/Page 12 of 24/March 2023
Meter boxes for "townhome" properties shall be set in grass area per Standard Detail 11AW
with the meter box and lid to meet the requirements of Tier 15 minimum load rating (ANSI)
for incidental traffic if less than 18” from a driveway.
When no alternative is available, a meter will be allowed in paved area and:
Top of box shall be flush with surface located outside of drainage flow lines (i.e., dry
surface area).
Meter box shall be placed out of a common traffic area. Bollards may be required under
certain conditions.
Meter box and lid shall meet the requirements of Tier 15 minimum load rating (ANSI)
for incidental traffic.
A 12” thick compacted rock base (3/4” washed rock) shall be required under the meter
box to prevent settlement. The base shall extend minimum 12” beyond the perimeter of
the meter box.
Locations for meter boxes and control valves shall be selected to be accessible and provide the
"minimum unobstructed space" shown on applicable details. Meter boxes shall be installed in
grass areas whenever possible and shall not be installed in pedestrian walkways, driveways or
inaccessible areas:
Minimum 12" horizontal separation is required between front edge of electrical
transformer pad or its projection and back edge of water meter box.
The Developer and/or his representative shall be responsible for coordination of locations
of services.
Meter/service will not be installed/activated until:
(1)
All form boards for driveway and /or sidewalk must be completely installed or the
driveway and/or sidewalk must have been installed
.
(2) A Wastewater lateral connection inspection was conducted.
(3) "Minimum unobstructed space" is provided as shown on applicable details.
(4) The required backflow prevention assembly/device is installed and has passed the
initial testing (if applicable).
(5) A signoff from the applicable Building Department has been obtained for a residential
fire line (NFPA Type 13d).
Minimum 5' horizontal separation is required between Potable Water service line and
Wastewater lateral.
Please note: that minimum 1” meters are required for services with NFPA Type 13d
residential fire lines.
(m) Meters shall not be placed in areas that can be fenced, such as backyards, under any
circumstances. Double boxes shall be used whenever possible for 5/8" X 3/4" meters with
3/4" fittings on or as close as possible to a common property line.
In cases where Potable Water, Reclaimed Water and Wastewater lines have been constructed
and a developer re-platted the development or relocated structures, the Department shall
require that services which cannot be reasonably adjusted, be removed and plugged at the main.
Potable Water Design Standards/Page 13 of 24/March 2023
If the number of services removed is excessive, the entire line may be required to be replaced.
A reasonable adjustment is considered to be less than 3 feet laterally. Any
adjustments/reconstruction shall be regarded as having to meet all new construction
requirements.
(n) Backflow Prevention Assemblies/Devices for Potable Water Services:
Backflow Prevention Assemblies/Devices shall be provided on all projects for prevention and
control of cross-connections. The backflow prevention assemblies/devices shall be University
of Southern California (USC) approved as required per Florida Administrator Code (FAC) 62-
555.360. All nonresidential services, services for buildings with more than three stories, and
residential services with 1-1/2” meters or larger shall have a Reduced Pressure Principle
Backflow Prevention Assembly. Residential Dual Check Valves (rdc) are required as a
minimum for all new residential Potable Water meters 1” and smaller and for existing
residential Potable Water services with master metered reclaimed water service. All Potable
Water services with individually metered reclaimed water service shall have a Reduced
Pressure Principle Backflow Prevention Assembly. There shall be no service connection
between the Backflow Prevention Assembly/Device and meter assembly.
All applicable Backflow Prevention Assemblies/Devices must be installed by the
Developer/Customer prior to Potable Water meter installation. The installation of the
assembly/device must follow the manufacturer’s guidelines. The assembly/device must be
easily accessible and have a minimum of 3’ clear space around it. The assembly/device shall
be located as close as possible to the Point of Service. Except for water services for Department
facilities, the testable Reduced Pressure Principle Backflow Prevention Assembly will remain
the property of the Customer, who shall also be responsible for installation, operation,
maintenance, and testing of the assembly following Service Activation. Multiple parallel
installed backflow prevention devices shall be designed for potable water connections where
service continuity is of utmost importance (for example: schools, treatment plants, etc.). For
additional information about application and acceptable Backflow Prevention Assemblies, see
Chapter 7 of the UPAP and Section 4.3 herein. In cases where a Reduced Pressure Principle
Assembly or Double Check Valve Detector Assembly type backflow preventer is required, the
Department shall perform the initial testing of the assembly and certify the installation for
compliance.
2.2 POTABLE WATER MAIN CONSTRUCTION
(a) Installation: Installation of Potable Water pipe and associated fittings shall be in accordance
with current AWWA and NSF standards and manufacturers' requirements for their particular
products. All non-DIP mains shall have a minimum of 36" clear cover to finished grade unless
specifically approved otherwise, subject to pipe material limitation, with the pipe installed as
level as possible.
Approved pipe joint restraint shall be required at each fitting involving a change of direction
and as specified in plan details. The contractor shall be responsible to ensure that all safety
requirements are met with respect to construction.
Potable Water Design Standards/Page 14 of 24/March 2023
Changes in pipe alignment may be accomplished using appropriate fittings or through pipe
deflection. Pipe deflection at the joint is allowed with ductile iron pipe and with specially
designed PVC pipes. (See Approved Material List). The deflection shall not exceed 75%
of the Manufacturer's recommended maximum joint deflection. No deflection at the joint is
allowed for PVC pipe unless allowed by the pipe manufacturer and does not exceed 75% of
the Manufacturer's recommended maximum joint deflection. If joint deflection is not
allowed, PVC pipe curvature shall be accomplished by installing appropriate bends. All pipes
shall be laid in trenches having a dry and stable bottom. Backfill shall be free of boulders and
debris. Pipe shall be fully supported along its entire length. Sharp or rocky material
encountered in the base shall be replaced with proper bedding. Pipe shall be laid on line and
grade as designed.
Fire hydrants shall be installed with the center of the pumper nozzle at 18" minimum to 24”
maximum above finished grade. Hydrants shall not be placed in sidewalks or traffic areas.
It will be the responsibility of the developer to move hydrants placed in an unacceptable
location and provide protection from traffic damage if necessary, upon the Department's
request. Concrete collars are required for hydrants in unpaved areas. Fire hydrants must be
ordered red in color. Fire hydrants must be clean and have a glossy red finish when accepted
by the utility. If painting is required all oil, grease, dirt, salts and other contaminants must be
removed. Two coats of approved paint to be applied by brush per manufacturer’s
specification for a DFT of at least 4 mils per coat.
All valves shall be placed according to plans unless relocation was been previously approved
by the Department prior to installation. Valves shall not be placed in curbs or gutters or in
designated parking spaces and shall be accessible at all times. As-built (record) drawings
shall reflect the actual location of all mains, hydrants, services, mechanically restrained pipe
and valves. All taps must be at least 18" from a fitting or bell. Potable Water mains shall not
be laid in fuel contaminated areas.
All road crossings, pavement cuttings and restoration shall be in accordance with the
requirements of the particular authority governing the area.
(b) Connection to Existing System:
All connections to existing Potable Water mains shall be made under the direct supervision
of the Department. Valves on existing Potable Water mains shall be operated by the
Department personnel or under direct supervision of the Department. The contractor shall
confirm the compliance of the existing facilities with the Standards and, modify the
facilities, if required, at no cost to the Department, prior to connection. Any modifications
to the existing facilities must be designed by the Project Engineer and with prior
Department approval. Tapping sleeve and valve shall be pressure tested using the test plug
on the tapping sleeve prior to tapping the water main. Insertion valves or temporary line
stops may be required in order to eliminate service interruptions. When installing an
insertion valve or line stop the existing water main must be restrained as a “dead end”
based Standard Detail 34W.
Potable Water Design Standards/Page 15 of 24/March 2023
If service must be temporarily shut off to existing Customers, the Department must have
minimum seven (7) business day notice to make necessary notifications and no shutdowns
can be scheduled for Fridays. The contractor or developer may be required to assist in
notifications. In this event, contractor shall be ready to proceed with as much material
preassembled as possible at the site to minimize the length of service interruption. The
Department will postpone a temporary service shut off if the contractor is not ready to
proceed on schedule. Such connections may have to be made at night to minimize effects.
No Customer should be without service for more than two (2) hours. Local chlorination
will be required for all pipe and fittings used to complete connections with existing potable
water main.
(c) Cleaning and Flushing:
Foreign material shall be kept out of pipe or cleaned from pipe prior to installation. The
ends of pipe installed during one day shall be capped at the end of each day with pipe plugs
to prevent contamination. Upon completion of installation and initial disinfection the mains
shall be flushed with potable water and the water disposed of without creating a nuisance.
Bypass piping is required for filling and initial disinfection. The existing potable water
main valve shall remain closed during the filling and initial disinfection. Bypass piping
shall include a minimum of two (2) single check valves. A tee with pressure gauge shall
allow for chlorine injection during filling and disinfection. A metering injection pump
shall be used to ensure a minimum of 50 ppm chlorine level. After the pipe is disinfected,
the existing valve and the tie-in valve in the potable water main shall be cracked open to
allow for flushing. A Department Inspector shall witness the filing and flushing through
the main pipe.
(d) Testing:
(1) Bacteriological Testing. New water mains shall be bacteriologically tested prior to pressure
testing unless “alternate” testing sequence is approved by the Department. The “alternate”
testing procedure allows for pressure testing ahead of bacteriological testing, and requires
double valving with a pressure gauge installed between the valves.
All new Potable Water mains shall be tested for bacteriological acceptability by a certified
laboratory and pressure tested using Potable Water. Sample points are required. Fire
hydrants shall be used as sample points whenever possible. Bacteriological testing is
generally required for any work involving a connection to the potable water system.
Bacteriological testing is required in order to certify the newly installed Potable Water main
to the Florida Department of Health Palm Beach County (Health Department). The test
results must be received by the Health Department within 60 days of collection date to be
valid. However, for the Department to except the test results and approve the DEP or PBCHD
Certification (final or construction water only) form they must be received within 30 days of
sampling. Only “construction meters” (hydrant meters) may be installed with “construction
water only release” from the Health Department. The water through construction meters
shall be considered non-potable and shall not be used for drinking or consumption purposes.
Potable Water Design Standards/Page 16 of 24/March 2023
“Construction water” may be used for non-potable applications such as temporary irrigation,
testing of internal plumbing systems, flushing toilets in model homes, construction trailers
and/or sales trailers. The Developer shall post “Non-Potable Water Do Not Drink” signs
at all water outlets served with construction water.
(2) Pressure Testing. New water mains shall be pressure tested after the “construction water
release” is received, record drawings, and fire flow tests are approved by the Department.
The road rock/base along with the “tack coatas required by the Department’s Inspector
shall be installed prior to pressure testing of water mains. Potable water shall be supplied to
the main and pumped to 150 psi or 200 psi for pipes larger than 24”.
The maximum length of line to be tested as one section will be 2,500 feet. HDPE pipe
segments shall be pressure tested separately from other pipe material (see Section 4.4.3{g}
for details). The test shall be performed as determined in the current AWWA specification
subject to specifications as listed below. The standard test duration is two (2) hours. The
maximum quantity of make-up water that must be supplied into the tested pipe to maintain
pressure within 5 psi of the specified test pressure shall not exceed 50% of the applicable
AWWA C-600 Standard. The make-up water for pressure testing shall consist of ½ ounce of
5% sodium hypochlorite per one gallon of Potable Water. If the pressure test fails, or if the
water main pressure drops below 20 psi after the initial bacteriological tests were conducted,
the bacteriological tests must be repeated before a request for “full release” certification is
issued to the Health Department.
(3) Fire Hydrant Flow Testing. A flow test to verify the fire flow rates shall be provided by the
Developer on all new fire hydrants and/or relocated fire hydrants. The fire hydrant fire flow
tests are required prior to the project’s final HRS Certification and only after “construction
water only” clearance is obtained from the Health Department and the new Potable Water
system has passed its required Department pressure test. The Fire Marshal Office or
designee having the jurisdiction shall perform all fire flow tests. The Fire Marshal may
accept test results for residential projects performed by a contractor when witnessed by a
utility inspector only when prior approval was provided by the Fire Marshal Office having
jurisdiction. Only accurate, calibrated pressure gauges (0-100 psi) shall be used for testing.
The gauges must “zero out” at the end of the test. The flow tests shall be witnessed by the
Department following the procedure as outlined below:
(a) Make provisions for minimizing interruptions to traffic and for adequate drainage of
water.
(b) Locate the residual hydrant and do the following:
Flush the residual hydrant to eliminate sediment that may damage the gauge.
(Always open and close hydrants SLOWLY to minimize water hammer).
Install the outlet-nozzle cap equipped with the pressure gauge on a hydrant
nozzle. A “Defuser” shall be used to minimize damage to landscaping, etc.
Open the main valve slowly until the air is vented. Close the vent and open the
main valve fully.
Read the gauge. This is the static pressure reading.
Potable Water Design Standards/Page 17 of 24/March 2023
(c) Conduct the flow test as follows:
Station one person at the residual hydrant and one person at each test hydrant.
Open each test hydrant SLOWLY until it is fully open. Open one hydrant at a
time to avoid a pressure surge.
When the pressure at the residual hydrant is stabilized, the person at the residual
hydrant signals the person stationed at the test hydrant to take the reading. The
readings for residual pressure and flow rate readings of each flow hydrant must
be taken simultaneously. The air should be exhausted from the flowing hydrant
before the reading is taken.
Record the residual reading and the flow reading at each test hydrant. Then
SLOWLY close the test hydrants one at a time.
For accurate test results, the pressure drop between the static and the residual pressures should
be at least 10 psi. If the pressure drop is less than 10 psi, an additional test hydrant should be
added to the test.
(4) Plot the flow results in the field utilizing appropriate graph so that if the results appear in error,
the test can be repeated immediately. Any inconsistencies in flows shall be verified and
corrected (if necessary) prior to final water system certification.
(5) The cumulative fire flow rate at 20 psi shall equal or exceed the minimum fire flow rate
required by the Fire Marshall.
(6) Backflow Prevention Assembly Testing: The Department shall perform the initial testing of the
assemblies and certify the installation and operation for compliance prior to Service Activation.
(e) Disinfection: All Potable Water mains shall be disinfected in accordance with AWWA
standards and Palm Beach County Public Health Unit regulations. Samples will be taken
from all sections of main and a clearance is required from the Health Department before the
main can be put in service.
(f) Handling, Abandonment and Disposal of Asbestos/Cement (AC) Pipe:
(1) All cutting, removal and disposal of AC pipe must be performed by a Florida licensed
Asbestos Abatement Contractor per applicable local, state and federal regulations. The
Department will make every reasonable effort to identify and quantify the location of known
AC pipe prior to onset of work. If the Contractor during the course of work observes,
uncovers, or otherwise becomes aware of the existence of any asbestos-cement pipe, pieces,
or material at the site to which the Contractor or any subcontractor, supplier, or other person
may be exposed, the Contractor shall immediately notify the Project Engineer and the
Department.
(2) On projects designed and/or constructed by the Department, the Contractor shall notify the
County’s Risk Management and Water Utilities Departments. The Risk Management
Department shall promptly consult with the Project Engineer concerning such condition and
Potable Water Design Standards/Page 18 of 24/March 2023
determine the necessity of the County retaining special consultants or qualified experts. The
contractor shall not perform any work near or in connection with the suspect material until
receipt of special written instructions from the Risk Management Department. The
Contractor will ensure that all subcontractors follow these procedures.
(3) Abandonment Grouting and/or abandonment in place is not permitted, unless otherwise
authorized by the County, written approval is required. AC pipe to be abandoned in place
shall be filled with grout. Abandoned A/C pipe is to be shown on the as-built drawings. The
grout mix shall be:
Cubic
Type Pounds Feet
Cement 340 1.73
Sand 2840 17.91
Stone 0 0
Water 374 6.00
Admix/Type B 13 oz.
Air 170 + 5.0% 1.35
The slump shall be 6" + 1 inch, Admix 1 shall meet ASTM C-494 type BD. Alternative
mixes will be considered.
2.3 CONSTRUCTION USING HORIZONTAL DIRECTIONAL DRILLING (HDD)
(a) General
Potable Water design and construction standards (Section 1, 2, 4) shall apply unless noted otherwise.
The Department reserves the right to disapprove a horizontal directional drilling installation if the
conventional open trench or jack and bore type installation is preferred by the Department, because:
Excessive number of high/low points
Excessive depth of pipe is of concern
A casing is required by the Department to protect the utility pipe
Future service and main connections to the utility pipe will be negatively impacted by a
horizontal directional drilling
(b) Pipe sizes, pipe material
The horizontal directional drilled utility main shall be manufactured approved restraint joint DIP,
PVC AWWA C-900 DR14, 200 psi, NSF 61 (4”-12”) or HDPE pipe (SDR 11).
If the directional-drilled pipe is to be used as a casing for a small diameter service line (up to 2”
Potable Water Design Standards/Page 19 of 24/March 2023
diameter), PVC DR18 or HDPE DR 17 pipes are is acceptable. Pipe and system components
shall be free from voids, cracks, inclusions, and other defects and shall be uniform in color
throughout the installation.
(c) Design Requirements
The Engineer shall inquire with the Department about approval of a horizontal directional drilling
procedure for a pipe installation. With the Department’s concurrence, the Engineer shall submit a
signed and sealed pilot bore plan for review and approval. The plan shall be submitted on a 24” x
36” sheet to a maximum 1”=20’ horizontal and 1”=2’ vertical scale (1”=10’ horizontal, 1”=10’
vertical scale preferred). The plan must show:
Finished grade and surface improvements
Locations of drill set-up
Length of bore
Deflection and radiuses of the pilot bore
Field verified locations of existing utilities and underground structures
Minimum horizontal and vertical clearances from underground structures, conduits, piping
systems (the proposed clearances must exceed the Department’s standards plus the guidance
system accuracy tolerance)
Pipe size and specifications (including restraining provisions against “pipe shrinkage”)
Proposed pilot bore pipe defection limits shall not exceed 75% of the maximum deflection
allowed by the pipe manufacturer
The drill radius of the final HDD pipe shall be minimum 30 pipe diameters, not exceeding 80%
of the max. bending radius as recommended by pipe manufacturer
Limits of directional bore installation
Limits of pressure testing
Connection to existing utilities
Rights-of-way limits, utility easements and temporary construction easements
Minimum pipe joint restraints at each end of pipe material transition from HDPE pipe
Tracer wires
Isolation valves and/or transition fittings/adapters
(d) Preconstruction Meeting
Upon approval of the pilot drill plan by the Department and obtaining all necessary permits for the
directional drilling, the Engineer shall schedule a preconstruction meeting with the Department in
accordance with Section 5 - Subsection 5.3 Pre-Construction Requirements of this Minimum
Design and Construction Standards. If the construction requires any field welding/fusion of HDPE
pipe and/or fittings, a Certificate of Completion of a pipe fitting manufacturer approved training
program is required. The Engineer and the Contractors performing the utility work shall attend the
meeting. The Licensed HDD Contractor shall provide references certifying minimum five (5) years
HDD experience.
Potable Water Design Standards/Page 20 of 24/March 2023
(e) Pilot Bore
The Engineer shall schedule the beginning of work with the Department a minimum of 3 days in
advance. The drill path shall be accurately surveyed and plotted to create an “as-built” drawing
(same scale as the pilot drill plan).
A high accuracy MGS (Magnetic Guidance System) shall be capable to provide vertical pipe data
with a max. + 2% deviation and horizontal pipe location data with max. + 2 foot deviation. The
data shall be collected at max. 25’ intervals. Deviation of more than + 2 feet vertically or
horizontally from the approved pilot bore plan shall be reported immediately to the project
engineer for evaluation. The Engineer shall evaluate the as-built data and confirm the compliance
with the design parameters. Deviation beyond approved parameters (depths, deflection radius,
separation to other utilities or structures) shall be brought to the attention of the Department.
The signed and sealed pilot bore “as-built” drawing shall be submitted to the Department for
review and approval if the “as-built” location differs substantially from the design plan.
(f) Pull back of carrier pipe
Upon approval of the pilot bore location by the Department; the pullback operation of the required
carrier pipe shall begin. The Contractor shall select the proper reamer type with the final hole
opening to be a maximum of 1.5 times the outside diameter of the largest component system.
The open borehole shall be stabilized by means of bentonite drilling slurry. The slurry shall be
contained at the entry or the exit side of the bore in pits or holding tanks.
The pipe sections shall be butt fused/joined together in accordance with the manufacturer’s
specifications. The ends of the pipe, gaskets and couplings shall be inspected for cleanliness.
Chipped, scratched, scraped, cracked or excessive deformed pipe or couplings shall be rejected.
Two approved APWA color coded HDD tracer wires shall be pulled along the sides of the product
pipe, and extended to nearest valve boxes (coil min. 3’ wire near the surface inside valve box).
The installation of the tracer wires is an essential part of the Horizontal Directional Drill process
and the contractor shall use all reasonable means and methods to insure that the tracer wires are
pulled without breakage. However, accidental tracer wire breakage shall not be a reason to require
a repeat directional drill unless specifically required in the project specifications.
The pipe shall be elevated to the approximate angle of entry and supported by roller arms or
equivalent. Any field welding/fusion of HDPE pipe and fittings may be performed only by
personnel certified through a pipe/fitting manufacturer approved training program.
(g) Testing
Pipe installed using the HDD method shall be flushed and pressure tested using Potable Water. The
pressure within the HDPE Pipe test section shall be raised to approx. 160 psi and then allowed to
idle for approximately 3 hours in order to allow to stabilize. Additional make-up water/pressure
Potable Water Design Standards/Page 21 of 24/March 2023
shall be applied during the 3 hour stabilization period only to maintain a minimum 140 psi
pressure.
The final phase of the pressure test shall involve applying make-up water/pressure to achieve a test
pressure of 150 psi or higher (as required). The test section is then allowed to idle (no make-up
water /pressure is added) for a period of 2 hours. After this 2 hour period, make-up water/pressure
is applied and measured to reestablish the test pressure. If the measured and added quantity of
water is greater than the allowable amount, the pressure test fails. No leakage is acceptable.
Installed services, tees and stub-outs shall be pressure tested together with the main. Pressure test
is not required if the installed pipe is intended to be used as a casing. If the pipe successfully passed
the pressure test, a connection to the existing pipe system may be performed. Bacteriological
testing is required.
(h) As-Builts
Certified as-built drawings (signed and sealed by a licensed professional land surveyor or
professional engineer full size paper copies and electronic files) must be submitted to the
Department for review and approval prior to any final certification in accordance with Section 6 -
Subsection 6.1 Record Drawings of this Minimum Design and Construction Standards.
Potable Water Design Standards/Page 22 of 24/March 2023
SECTION 2.4 - POTABLE WATER SYSTEM STANDARD DETAILS LISTING
1W POTABLE WATER SERVICE SINGLE 5/8" X 3/4" AND 1" METER INSTALLATION (PVC)
2W POTABLE WATER SERVICE SINGLE 5/8" X 3/4" AND 1" METER INSTALLATION
(POLYETHYLENE)
3W POTABLE WATER SERVICE DUAL 5/8" X 3/4" METER INSTALLATION (PVC)
4W POTABLE WATER SERVICE DUAL 5/8" X 3/4" METER INSTALLATION (POLYETHYLENE)
5W POTABLE WATER TYPICAL CONNECTION FOR MULTIPLE SERVICES
6W POTABLE WATER 1-1/2" METER INSTALLATION
7W POTABLE WATER 2" METER INSTALLATION
8WA POTABLE WATER 3" METER INSTALLATION (RESIDENTIAL ONLY)
8WB POTABLE WATER 3" METER INSTALLATION (NON-RESIDENTIAL ONLY)
9W POTABLE WATER 4" METER INSTALLATION
10W POTABLE WATER 6" METER INSTALLATION
11WA TYPICAL UTILITY INSTALLATION DETAIL IN A 10' UE PARALLEL TO R/W
11WB METER BOX INSTALLATION DETAIL BETWEEN TOWNHOME DRIVEWAYS
12W TYPICAL FIRE HYDRANT INSTALLATION WITH BOLLARDS DETAIL
13W POTABLE WATER MAIN TYPICAL GATE VALVE SETTING AND MAIN CUT-IN DETAIL
14W POTABLE WATER MAIN TYPICAL BUTTERFLY VALVE SETTING
15W PERMANENT SAMPLE POINT
16W POTABLE WATER MAIN TEMPORARY SAMPLING POINT
17W POTABLE WATER MAIN FIRE HYDRANT SAMPLING POINT
18W POTABLE WATER MAIN CROSSING OTHER MAINS AND UTILITES
19W POTABLE WATER MAIN CONFLICT DEFLECTION DETAIL
20W TYPICAL THRUST BLOCKS FOR PRESSURE PIPE
21W TYPICAL 2" TERMINAL BLOWOFF POTABLE WATER DISTRIBUTION MAINS
22WA POTABLE WATER MAIN CASING INSTALLATION DETAIL
22WB POTABLE WATER MAIN SPLIT CASING INSTALLATION DETAIL
23W POTABLE WATER TRENCH DETAIL
24W OPEN CUT PIPE INSTALLATION - NON-THOROUGHFARE ROAD
25W OPEN CUT PIPE INSTALLATION - THOROUGHFARE ROAD
26W POTABLE WATER MAIN TYPICAL AERIAL CANAL CROSSING - SINGLE PIPE (SINGLE
PILES)
27W FAN GUARD/PILE CAP DESIGN - SINGLE PIPE (SINGLE PILES)
28W POTABLE WATER MAIN UNDERGROUND AIR RELEASE VALVE & VAULT IN
NON-TRAFFIC AREAS OUTSIDE OF ROAD RIGHTS-OF-WAY
29W POTABLE WATER MAIN AIR RELEASE MANHOLE IN PAVED AREA AND IN ROAD
RIGHT-OF-WAY
30W POTABLE WATER MAIN OFF-SET UNDERGROUND AIR RELEASE VALVE
31W POTABLE WATER MAIN PRESSURE TEST CRITERIA
32W DOUBLE CHECK DETECTOR ASSEMBLY
33W STANDARD POTABLE WATER MAIN TIE-IN
34W MECHANICAL THRUST RESTRAINT-MINIMUM PIPE LENGTHS
35W UNDERGROUND PIPELINE SIGN DETAIL
36W SINGLE UNDERGROUND PIPELINE SIGN DETAIL
37W DUAL UNDERGROUND PIPELINE SIGN DETAIL
38W LWDD-SINGLE PIPE PARALLEL INSTALLATION (UNDERGROUND PIPELINE SIGN
INSTALLATION DETAIL)
Potable Water Design Standards/Page 23 of 24/March 2023
SECTION 2.4 - POTABLE WATER SYSTEM STANDARD DETAILS LISTING (cont'd)
39W LWDD-DUAL PIPE PARALLEL INSTALLATION (UNDERGROUND PIPELINE SIGN
INSTALLATION DETAIL)
40W LWDD-SINGLE PIPE SUBAQUEOUS CROSSING (UNDERGROUND PIPELINE
INSTALLATION DETAIL)
41W LWDD-DUAL PIPE SUBAQUEOUS CROSSING (UNDERGROUND PIPELINE SIGN
INSTALLATION DETAIL
42W ALTERNATE POTABLE WATERMAIN TIE-IN DETAIL
43W AUTOMATIC FLUSHING ASSEMBLY (TYPE A)
44W AUTOMATIC FLUSHING ASSEMBLY (TYPE B)
45W RIP-RAP INSTALLATION
46W LANDSCAPE AND ROOT BARRIER DETAIL
47W ABOVE GROUND WATER METER INSTALLATION PIPE SUPPORT
48W POTABLE WATER MAIN CROSSING FENCE, WALL, OR BERM CASING DETAIL
49W POTABLE WATER MAIN CONFLICT STRUCTURE DETAIL
Potable Water Design Standards/Page 24 of 24/March 2023
POTABLE WATER SYSTEM
STANDARD DETAILS SHEETS 1W - 49W