GENERAL REGULATIONS
16
mm) measured at the threshold. Where a threshold of at least
2 inches (51 mm) high does not exist, a temporary threshold
shall be constructed to retain the test water in the lined floor
or receptor area to a level not less than 2 inches (51 mm) deep
measured at the threshold. The water shall be retained for a
test period of not less than 15 minutes, and there shall not be
evidence of leakage.
312.10 Inspection and testing of backflow prevention
assemblies. Inspection and testing shall comply with Sec-
tions 312.10.1 and 312.10.2.
312.10.1 Inspections. Inspections shall be made of all
backflow prevention assemblies and air gaps to determine
whether they are operable.
312.10.2 Testing. Reduced pressure principle, double
check, pressure vacuum breaker, reduced pressure detector
fire protection, double check detector fire protection, and
spill-resistant vacuum breaker backflow preventer assem-
blies and hose connection backflow preventers shall be
tested at the time of installation and immediately after
repairs or relocation. The testing procedure shall be per-
formed in accordance with one of the following stan-
dards: ASSE 5013, ASSE 5015, ASSE 5020, ASSE 5047,
ASSE 5048, ASSE 5052, ASSE 5056, CSA B64.10 or
CSA B64.10.1.
SECTION313
EQUIPMENT EFFICIENCIES
313.1 General. Equipment efficiencies shall be in accor-dance with
the
Florida Building Code, Energy Conservation.
SECTION 314
CONDENSATE DISPOSAL
[M] 314.1 Fuel-burning appliances. Liquid combustion by-
products of condensing appliances shall be collected and dis-charged
to an approved plumbing fixture or disposal area in accordance with
the manufacturer’s instructions. Condensate piping shall be of
approved corrosion-resistant material and shall not be smaller than
the drain connection on the appli-ance. Such piping shall maintain a
horizontal slope in the direction of discharge of not less than one-
eighth unit vertical in 12 units horizontal (1-percent slope).
[M] 314.2 Evaporators and cooling coils. Condensate drain
systems shall be provided for equipment and appliances con-taining
evaporators or cooling coils. Condensate drain sys-tems shall be
designed, constructed and installed in accordance with
Sections 314.2.1 through 314.2.5.
[M] 314.2.1 Condensate drainage collection, use or disposal.
Condensate from all cooling coils and evaporators of equipment
served by an onsite cooling tower in a building or structure
wherein the aggregate cooling capacity of the equipment
exceeds 65,000 Btu/hr shall be collected and conveyed from the
drain pan outlet and discharged to the cooling tower. Where an
on-site cooling tower is not installed the condensate from all
cooling coils and evaporators shall be conveyed from the
drain pan outlet to an approved place of disposal. Such piping
shall maintain a horizontal slope in the direction of discharge of
not less than one-eighth unit vertical in 12 units horizontal (1-
percent slope). Condensate shall not discharge into a street,
alley or other areas so as to cause a nuisance.
[M] TABLE 314.2.2
CONDENSATE DRAIN SIZING
For SI: 1 inch = 25.4 mm, 1 ton of capacity = 3.517 kW.
[M] 314.2.3 Auxiliary and secondary
drain systems. In addition
to the requirements of Section 314.2.1, where damage to any
building components could occur as a result of overflow from the
equipment primary condensate removal system, one of the following
auxiliary protection methods shall be provided for each cooling
coil or fuel-fired appliance that produces condensate:
2. A separate overflow drain line shall be connected to the
drain pan provided with the equipment. Such overflow drain
shall discharge to a conspicuous point of disposal to alert
occupants in the event of a stoppage of the primary drain.
The overflow drain
EQUIPMENT CAPACITY
MINIMUM CONDENSATE
PIPE DIAMETER
(inch)
Up to 20 tons of refrigeration
3
/
4
inch
Over 20 tons to 40 tons of refrigeration 1 inch
Over 40 tons to 90 tons of refrigeration 1
1
/
4
inch
Over 90 tons to 125 tons of refrigeration 1
1
/
2
inch
Over 125 tons to 250 tons of refrigeration 2 inch
FLORIDA BUILDING CODE — PLUMBING, 6th EDITION
(2017)
Adopted: October 12, 2017
Effective: January 1, 2018
Exceptions:
1. Condensate from cooling coils and evaporators is not
required to be collected and conveyed to an on-site cooling
tower: provided 1.1 through 1.3 are met:
2.
In existing buildings condensate may be collected and
conveyed to a cooling tower or discharged to an approved
place of disposal.
1.1 The equipment comprises 10% or less of the total
capacity of the cooling tower system
1
.2 The equipment is located in an isolated or remote area
1.3 The size of the equipment is 65,000 Btu/hr or less
[M] 314.2.2 Drain pipe materials and sizes. Components of the
condensate disposal system shall be cast iron, galvanized steel,
copper, cross-linked polyethylene, polyethylene, ABS, CPVC or
PVC or polypropylene pipe or tubing. All components shall be
selected for the pressure and temperature rating of the pressure and
temperature rating of the installation. Joints and connections shall
be made in accordance with the applicable provisions of Chapter 7
relative to the material type. Condensate waste and drain line size
shall be not less
than 3/4-inch (19.1 mm) internal diameter shall
not decrease in size from the drain pan connection to the place of
the condensate disposal. Where the drain pipes from more than
one unit are manifolded together for condensate drainage, the pipe
or tubing shall be sized in accordance with Table 314.2.2.
1. An auxiliary drain pan with a separate drain shall be
provided under the coils on which condensation will occur.
The auxiliary pan drain shall discharge to a conspicuous point
o
f disposal to alert occupants in the event of a stoppage of the
primary drain. The pan shall have a depth of not less than
1
1/2
inches (38 mm), shall be not less than 3 inches (76 mm)
larger than the unit or the coil dimensions in width and length
and shall be constructed of corrosion-resistant material.
Galvanized sheet metal pans shall have a thickness of not less
than 0.0236-inch (0.6010 mm) (No. 24 gage) galvanized
sheet metal. Nonmetallic pans shall have a thickness of not
less than 0.0625-inch (1.6 mm)